Steam Demand Calculation
Steam Demand Calculation
Steam Demand Calculation
Steam Consumption by Equipment
The table below shows typical values of steam pressure, capacity, and estimated steam consumption (kg/h) for different process and equipment types.
| Equipment Type | Process Type | Steam Pressure (bar) | Capacity | Steam Consumption (kg/h) |
|---|---|---|---|---|
| PROCESS GROUP | ||||
| Copper Wire Drawing | — | 0.5 | Per machine | 20 |
| Aluminum Anodizing (Hot Sealing) | — | 6 | Per 1 m³ bath | 16 |
| Aluminum Anodizing (Cold Sealing) | — | 6 | Per 2 m³ bath | 12 |
| Timber Drying (hardwood, 75% humidity) | — | 6 | Per 1 m³ wet timber | 4.5 |
| Timber Drying (softwood, 75% humidity) | — | 6 | Per 2 m³ wet timber | 8 |
| Corrugated Cardboard Production | — | 12 – 14 | Per 1 kg/h cardboard | 0.25 |
| Milk Pasteurization | — | 0.5 | Per 1 kg milk/h | 0.17 |
| Liquid Egg Pasteurization | — | 1.5 | Per 1 kg egg/h | 0.12 |
| Concrete Curing | — | 4 – 5 | Per 1 m³ concrete/h | 20 |
| Concrete Curing (5-hour curing) | — | 4 – 5 | Per 1 m³ concrete/h | 20 |
| Wooden Pallet Curing (5-hour process) | — | 6 | Per 1 m³ pallet material | 25 |
| INDUSTRIAL KITCHEN EQUIPMENT | ||||
| Cooking Pot | — | 0.5 | 100 | 40 |
| Cooking Pot | — | 0.5 | 150 | 50 |
| Cooking Pot | — | 0.5 | 200 | 60 |
| Cooking Pot | — | 0.5 | 300 | 70 |
| Cooking Pot | — | 0.5 | 400 | 80 |
| Cooking Pot | — | 0.5 | 600 | 100 |
| Tea Boiler | — | 0.5 | 50 | 25 |
| Tilting Cooking Pot | — | 0.5 | 20 | 20 |
| Tilting Cooking Pot | — | 0.5 | 40 | 25 |
| Tilting Cooking Pot | — | 0.5 | 60 | 35 |
| INDUSTRIAL IRONS | ||||
| Roller Iron – 1.8 m · Ø 60 cm | — | 4 – 5 | 60 kg laundry/h | 75 |
| Roller Iron – 2.0 m · Ø 60 cm | — | 4 – 5 | 75 kg laundry/h | 100 |
| Roller Iron – 2.0 m · Ø 75 cm | — | 4 – 5 | 100 kg laundry/h | 125 |
| Roller Iron – 2.0 m · Ø 75 cm | — | 4 – 5 | 120 kg laundry/h | 150 |
| Roller Iron – 2.5 m · Ø 85 cm | — | 4 – 5 | 200 kg laundry/h | 200 |
| Roller Iron – 3.0 m · Ø 85 cm | — | 4 – 5 | 225 kg laundry/h | 250 |
| Form Finisher Iron | — | 4 – 5 | — | 30 |
| Trouser Finisher Iron | — | 4 – 5 | — | 35 |
| Press Iron | — | 4 – 5 | — | 16 – 28 |
| Hand Iron | — | 4 – 5 | — | 2 – 5 |
| Robot Iron | — | 4 – 5 | — | 30 |
| WASHING / CLEANING MACHINES | ||||
| Laundry Washing Machine | — | 4 – 5 | 20 kg laundry/h | 25 |
| Laundry Washing Machine | — | 4 – 5 | 40 kg laundry/h | 35 |
| Laundry Washing Machine | — | 4 – 5 | 60 kg laundry/h | 50 |
| Laundry Washing Machine | — | 4 – 5 | 100 kg laundry/h | 80 |
| Laundry Washing Machine | — | 4 – 5 | 150 kg laundry/h | 100 |
| Jeans Washing Machine | — | 4 – 5 | 300 kg laundry/h | 120 |
| Stain Removal Machine | — | 4 – 5 | — | 5 |
| Dry Cleaning Machine | — | 4 – 5 | 1 kg laundry/h | 0.5 |
| FABRIC / ZIPPER DYEING TANK | ||||
| Fabric / Zipper Dyeing Tank | — | 8 | 5 kg | 15 |
| Fabric / Zipper Dyeing Tank | — | 8 | 10 kg | 20 |
| Fabric / Zipper Dyeing Tank | — | 8 | 15 kg | 25 |
| Fabric / Zipper Dyeing Tank | — | 8 | 20 kg | 35 |
| Fabric / Zipper Dyeing Tank | — | 8 | 30 kg | 55 |
| Fabric / Zipper Dyeing Tank | — | 8 | 50 kg | 70 |
| Fabric / Zipper Dyeing Tank | — | 8 | 100 kg | 150 |
| DRYING MACHINES | ||||
| Laundry Dryer | — | 4 – 5 | 20 kg laundry/h | 25 |
| Laundry Dryer | — | 4 – 5 | 30 kg laundry/h | 35 |
| Laundry Dryer | — | 4 – 5 | 40 kg laundry/h | 45 |
| Laundry Dryer | — | 4 – 5 | 60 kg laundry/h | 65 |
| Laundry Dryer | — | 4 – 5 | 100 kg laundry/h | 110 |
| Laundry Dryer | — | 4 – 5 | 150 kg laundry/h | 160 |
| Jeans Dryer | — | 4 – 5 | 160 kg jeans/h | 400 |
| HEATING | ||||
| Fuel Oil Heating (1 °C temperature rise) | — | 5 | 1 kg fuel oil/h·°C | 0.001 |
| Water Heating (1 °C temperature rise) | — | 4 | 1 L water/h·°C | 0.002 |
| Air Heating (1 °C temperature rise) | — | 4 | 100 Nm³ air/h·°C | 0.075 |
| Building Heating | — | 0.5 – 4 | 1 m³ volume/h | 0.08 |